Protection
Protection Module Configuration with IMx-M Manager
2 - 172
SKF Multilog On-Line System IMx-M
User Manual
Figure 2 - 141.
Configuring Gap Sensor.
The
Sensitivity
is set to 7.87 mV/µm (200 mV/mil) to match the sensor
output.
The
Sensor OK Setting
levels are configured to -18 and -2 volts, to enable
usage of as much as possible of the probes linear range.