Protection
IMx-M Manager
SKF Multilog On-Line System IMx-M
2 - 87
User Manual
Status
Status displays the slot status and circuit fault results.
Figure 2 - 60.
Maintenance View - Slot Status.
Manager File CRC
is the IMx-M Manager configuration file CRC of the slot that
Maintenance View was selected from the hierarchy view. The CRC is assigned when
the configuration file is saved.
PRM CRC
is from the configuration file (.bin) that is in use by the protection
module. This configuration is the one Maintenance view will be using.
During the Maintenance mode, when any configuration change is needed, first
check to see if the Manager File CRC is the same as this PRM CRC. If they are the
same, changes can be made directly in the Manager. However, if they are not the
same, first this PRM configuration file must be imported to the Manager before any
changes can be made. Refer to
Getting Protection Configuration from Protection
, then restart the Maintenance View.
If any changes were made, remember to
send the changed slot configuration file to
PRM Firmware
is the FW in use by PRM
PRM Serial No.
is the PRM HW serial number
Connection IP
is the network address of the CMM + PRM slot which is in use. This
address (CMM IP-ADDRESS) is shown via
option under
Local Display Selection Keypad
Manager config IP
is the network address of the slot for which Maintenance View
was opened. This is the property of CMM + PRM slot setting.