Protection
Protection Module Configuration with IMx-M Manager
SKF Multilog On-Line System IMx-M
2 - 171
User Manual
Figure 2 - 140.
Configuring Alarms for Speed.
GAP
Configuring GAP Alarms
In this example, the main measurement has been configured to be a
measurement of radial shaft vibration but could as well have been eccentricity.
Scenario: ”During the installation of the probe the probe gap was adjusted to
produce an output of about -10 volts. Measuring the output voltage with a
quality precision voltmeter gives a Gap voltage of -10083 mV, which is
accepted as close enough to the center of the probe linear output range.”