4.11 Operating modes of the EDL1
The EDL1 has 3 operating modes. These facilitate an adaptation to the different operating modes and controls.
4.12 ON/OFF mode
Cycle time
approx. 60 seconds
Lubrication time
approx. 15 seconds
Lock-out time
45 seconds
Duty cycle
>
60 seconds
Additional lubrication cycle
possible within lock-out time
YES
Pause time
KEINE
Setting the mode via DIP switches
DIP switch 7
Position 0
Variable DIP switches for this mode
DIP switch 6
Position 0 or 1
1
ON
2 3 4 5 6 7 8
1
0
9
Application example:
Each time the power supply of the EDL1
is switched on, a lubrication cyle shall be
performed.
Setting the ON/OFF mode, see chapter 6.7.
To carry out another lubrication
cycle, the power supply of the
EDL1 must be switched off and
on again.
ON/OFF mode Fig. 10
1
Power 24 V DC
2
Mass (-)
3 PE
8/9
Fault signal
(potential-free)
10/11 Feedback (potential-free)
(lubrication cycle successfully completed)