MultiXplo / MultiTox
Page 42 / 60
NOSP15759-Rev 10
6.7.5.
Output configuration sub-menu
[Adjust] / [Config] / [Outputs]
This menu gives access to the configuration of the relay operating mode and to conditions of
activations.
State of the relays:
Each relay can be configured:
•
Normally open (not energized)
•
Normally closed (energized)
Activation of the relays:
Each relay can be activated on one or several following conditions:
•
Alarm
•
Fault
•
Inhibition
Factory setting:
•
Relay 1:
normally not energized, activated on alarm levels
•
Relay 2:
normally energised, activated by any fault or inhibition
Contacts are then described as below
:
Detector status
Relay 1
“Alarm”
Relay 2
“Fault”
Normal
(no alarm, no fault, no inhibition
and detector powered
C1-T1 open
C2-T2 closed
Alarm
C1-T1 closed
C2-T2 closed
Ambiguity function
(TX explosimeter only)
C1-T1 closed
C2-T2 open
Fault or inhibition
C1-T1 open
C2-T2 open
Maintenance Inhibition
(during maintenance mode)
Depend of configuration. See chapter 6.2
Power loss
C1-T1 open
C2-T2 open
Output current configuration
This menu allows you to switch the format of the output current between 4-20 mA and 0-22
mA
.
Factory setting: the output current is 4-20 mA
Summary of Contents for DM-TT6-K
Page 9: ...MultiXplo MultiTox Page 9 60 NOSP15759 Rev 10 Figure 1 Layout Drawing Congestion see Figure 2...
Page 32: ...MultiXplo MultiTox Page 32 60 NOSP15759 Rev 10...
Page 48: ...MultiXplo MultiTox Page 48 60 NOSP15759 Rev 10...
Page 56: ...MultiXplo MultiTox Page 56 60 NOSP15759 Rev 10 10 CONFORMITY CERTIFICATE...
Page 57: ...MultiXplo MultiTox Page 57 60 NOSP15759 Rev 10...
Page 58: ...MultiXplo MultiTox Page 58 60 NOSP15759 Rev 10...
Page 59: ...MultiXplo MultiTox Page 59 60 NOSP15759 Rev 10...