MultiXplo / MultiTox
Page 28 / 60
NOSP15759-Rev 10
4.3.10.
0-22mA input connection
In one of its inputs type, type (C): DM-**6-****-C**-**-***-*-*-* the device enables to use a
0-22mA input from another sensor.
In that case, an inputs of the cable gland or an accessory in replacement of the cartridge
enables the connection between the hosted sensor and the device.
In order to operate this analogue input, an additional electronic card (PIE 3508 or PIE 3509) is
added above the numeric card
The hosted sensor NEEDS to get its own power
The connecting wires to another detector are limited to a 1 mm² section.
Using this board leads to a connection between 0V from power supply and housing
ground.
Connection to detector
RS485 :
Terminal block
not used