4.
INSTALLATION
Detectors described in this manual are safety instruments intended to be installed in
explosive atmospheres and have been designed in compliance with standards EN60079-0
and EN60079-1, EN 60079-29-1, CEI 60079-0 and CEI 60079-1.
Intervention in some sites may be subject to restrictions that we invite you to
follow for your own safety and those of others.
4.1.
Positioning
The detector must be positioned as close as possible to sources of potential leakage, taking
into account airflows (e.g. upper and lower ventilation). The height is determined by the
density of the gas to detect.
Generally speaking, a detector will not be placed in front of an air inlet that brings clean air
This height may be adjust to take into account the specific conditions which may interfere on
the risk level (gas density, ambient temperature…)
There are no limit positions of the detector however it is recommended to position
the detector vertically (ie with the cartridge pointing downwards).
Air velocity limits: 6 m/s.