MultiXplo / MultiTox
Page 7 / 60
NOSP15759-Rev 10
1.
PRODUCT DESCRIPTION
The DM-TX6-X is designed to monitor explosions hazard induced by the presence of
flammable gases or vapours (hydrogen, hydrocarbons, alcohol, etc…).
The DM-TT6-K is designed to monitor the gas concentration in %vol. induced by the presence
of some special gases or vapours (hydrogen, helium, carbon dioxide, etc…).
The detector can be connected directly to a large range of traditional controllers or
Programmable Logic Controllers (PLC).
The DM-TX6-X and the DM-TT6-K may be fully configured using the portable communication
terminal (TLU600) in ATEX areas, providing flexibility to the user.
These detectors can be configured also using the Hart portable terminal TLH700 (in option).
The MultiXplo and MultiTox are also available for use in an addressable network system with
distributed intelligence, SYNTEL. For more information, please refer to the Syntel module
interface operating manual.
1.1.
Application Fields
The DM-TX6-X and the DM-TT6-K are suitable for indoor and outdoor uses and offer a fast
response time. Typical applications include:
•
Storage and use of combustible/flammable gases and
vapours(DM-TX6-X),
•
Monitoring of processes with flammable products
•
Hydrogen detection in inert atmosphere and in high
concentration (DM-TT6-K),
•
Chemical and petrochemical plants
•
Pharmaceutical industry
•
LNG/LPG
•
Oil and gas facilities
1.2.
DM-TX6-X
The detectors are calibrated on 100% LEL (Lower Explosive Limit) of a particular gas or
vapour.
The DM-TX6-X is a MultiXplo detector based on a transducer with thermo-catalytic oxidation,
which requires oxygen to function properly.
In the event of a long period without oxygen, the measurement will no longer be
representative of the concentration of gases or vapours.
The characteristics of the device can also be altered by the presence of certain catalyst
poisons such as silicone fumes, vapours of organometallic compounds and, to some extent
by halogenated compounds.
Summary of Contents for DM-TT6-K
Page 9: ...MultiXplo MultiTox Page 9 60 NOSP15759 Rev 10 Figure 1 Layout Drawing Congestion see Figure 2...
Page 32: ...MultiXplo MultiTox Page 32 60 NOSP15759 Rev 10...
Page 48: ...MultiXplo MultiTox Page 48 60 NOSP15759 Rev 10...
Page 56: ...MultiXplo MultiTox Page 56 60 NOSP15759 Rev 10 10 CONFORMITY CERTIFICATE...
Page 57: ...MultiXplo MultiTox Page 57 60 NOSP15759 Rev 10...
Page 58: ...MultiXplo MultiTox Page 58 60 NOSP15759 Rev 10...
Page 59: ...MultiXplo MultiTox Page 59 60 NOSP15759 Rev 10...