MultiXplo / MultiTox
Page 34 / 60
NOSP15759-Rev 10
6.3.
Signal current loop
State
“4-20”
[mA]
“0-22”
[mA]
TLU state
Line fault
0.0
0.0
Configuration fault
2.0
2.0
DEF
Detector fault (electronic)
2.0
2.0
DEF
Measure fault
2.0
2.6
DEF
Start inhibition
2.0
3.4
Warming up
remaining time
including power up
Permanent inhibition
2.0
3.4
INH
Maintenance inhibition
Fixed configuration (fault) / (“free mode ”) *
Previous value/
(2.0)
Previous value/
(3.4)
INH
Alarm verification
21.7
21.7
DOUT
0% of full scale
4.0
4.0
No detection
No alarm
25% of full scale
8.0
8.0
Alarm if overran
level
50% of full scale
12.0
12.0
Alarm if overran
level
75% of full scale
16.0
16.0
Alarm if overran
level
100% of full scale
20.0
20.0
Alarm
105% of full scale
20.8
20.8
Alarm
(*) Maintenance inhibition may be available in frozen or free mode
.
6.4.
Alarm indication (LED)
A red LED located in the head of communication flashes in case of confirmed alarm status.
•
Flashing 1 Hz: Level 1
•
Flashing 3 Hz: Level 2
If the alarm memorization is activated, the LED continues to flash until the alarm is
acknowledged with the TLU or until the detector is powered off, then powered on again.
If the alarm memorization is disabled, the LED stops flashing when the alarm fades.
If the device is used in a safety loop in a potentially explosive area (EN60079-29-1),
the upper alarm must be memorized, and a manual action must be taken to clear
it.
6.5.
Wireless communication tool TLU600
All settings and tests of detectors can be done by the wireless communication tool TLU600.
This communication tool and its software are compatible with all Oldham Simtronics
detectors: MultiFlame, MultiTox and MultiXplo. Communication is made via infrared link
(IrDA), similar but more efficient than infrared links for computers. IrDA head should not be
placed facing the sun as it significantly reduces the communication with the TLU600.
Please refer to the wireless communication tool operating manual for more details.
Summary of Contents for DM-TT6-K
Page 9: ...MultiXplo MultiTox Page 9 60 NOSP15759 Rev 10 Figure 1 Layout Drawing Congestion see Figure 2...
Page 32: ...MultiXplo MultiTox Page 32 60 NOSP15759 Rev 10...
Page 48: ...MultiXplo MultiTox Page 48 60 NOSP15759 Rev 10...
Page 56: ...MultiXplo MultiTox Page 56 60 NOSP15759 Rev 10 10 CONFORMITY CERTIFICATE...
Page 57: ...MultiXplo MultiTox Page 57 60 NOSP15759 Rev 10...
Page 58: ...MultiXplo MultiTox Page 58 60 NOSP15759 Rev 10...
Page 59: ...MultiXplo MultiTox Page 59 60 NOSP15759 Rev 10...