NOSP15759-Rev 10
4.3.8.
EOL Resistor
This applies to ATEX/IEC installations only. The EOL resistor must only be used
inside the housing on the terminal block.
The EOL resistor allows to a detection unit equipped with the line control function to ensure
the continuity of the relay cable.
The EOL resistor must be placed on the relay contact connector to be monitored.
Maintain a 10mm minimum gap between the resistor and the terminal block or any other
neighboring parts.
NB :
The R1 value is given as an indication. It must comply with the following conditions:
•
Minimum consumption = 5 Watts
•
Maximum dissipation = 2.5 Watts