Chapter 8. Operating
8-5
Setting the Time and Date
Selecting the "Set Time/Date" option from the main menu
allows you to change the system time and date. This opera-
tion is protected at Access Level 2.
<ENTER>=Accept
[11]:23 pm 11/12/03
The Right/Left arrow keys allow you to move the focus from
field-to-field for editing. The <NEXT/PREV> keys allow
you to change the currently selected fields. The am/pm field
and the day-of-week field are not editable.
Reports
Reports, which are either text-based archives of system
activity or a text-based description of the panel configura-
tion, can be archived and printed in the following manner.
•
The panel supports an unsupervised, 80-column serial
printer that can be used to record events, or to print his-
tory log reports.
•
Use Windows Hyperterminal (or similar application), as
follows:
a.
Connect a 733-794 download cable between the
Service Port on the panel and a serial communica-
tion port on the PC.
a.
Create a connection profile for the serial port. Set
the serial communication parameters to 9600 baud,
8 bits, no parity, 1 stop bit, and no flow control.
a.
Configure the application to capture the informa-
tion coming in on the serial port. (Choose Capture
Text in the Hyperterminal Transfer menu.)
To generate a report, do the following.
1.
Press <MENU>.
2.
Press <NEXT> and <PREV> until the following
prompt appears.
<ENTER>=Accept
Menu: [Reports]
3.
Press <ENTER>. A prompt similar to the following
appears.
<ENTER>=Accept
Rep: [ALOG]
4.
Use the <NEXT> or <PREV> key to select one of the
options described in Table 8-4.
5.
Press <ENTER>. The panel displays a message noting
that the report has been sent to the printer.
Diagnostics
Use the following procedure to run the panel’s diagnostic
options.
1.
Press <MENU>.
2.
Press <NEXT> and <PREV> until the following
prompt appears.
Control Point
Bypass
Bypasses the following control points
(causes a trouble):
•
On-til-Silence NACs
•
On-til-Reset NACs/relays
Elevator
Bypass
Bypasses Elevator Recall operation
(causes a trouble)
Doorholder
Bypass
Bypasses the door holder operation
(causes a trouble)
Lamp Test
Illuminates all LEDs and LCD segments
on the operator interface.
Earth Fault
Latch
Latches intermittent Earth troubles in the
panel, preventing them from automati-
cally clearing.
Display Time
Shows the current time and date.
Send DACT
Test
Sends the DACT test event to the sta-
tionary station.
Table 8-3 Control Functions (Continued)
Function
Description
Table 8-4 Reports
Report
Description
ALOG
Displays contents of alarm log.
SLOG
Displays contents of supervisory log.
TLOG
Displays contents of trouble log.
CLOG
Combined alarm, supervisory, and trou-
ble logs.
CONFIG
Text description - including custom label,
function type
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...