Chapter 4. Manually Programming IDNet Points
4-2
Accessing IDNet Programming
Menus
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press <ENTER>. The Programming menu appears:
<ENTER>=Accept
Prg:[Points]
3.
Press Enter again. A prompt appears, allowing you to
select the type of point to manually edit. By default,
IDNet is the first choice.
<ENTER>=Accept
Prg: [IDNet]
4.
Press <ENTER>.
<ENTER>=Accept
IDNet: [Add]
5.
Use The <NEXT> and <PREV> keys to scroll through
the following choices and then press <ENTER>.
•
Edit-
change the characteristics of an existing
IDNet device:
•
Add
- add a new IDNet device at an unused address.
•
Delete
- remove a configured IDNet device from the
system.
Select the operation you want to perform and see the appro-
priate section in this chapter.
Adding an IDNet Device
Follow the steps outlined in “Accessing IDNet Program-
ming Menus.” Select “Add” and then press <ENTER>. The
display appears similar to the following.
<ENTER>=Accept
IDNet: 2
Use the <NEXT> and <PREV> keys to scroll through the
list of device addresses. When the appropriate address is dis-
played, press <ENTER>.
Note
: Make sure the address shown on the display corre-
sponds to the physical address, set via dip switches, of the
device.
Refer to “Editing IDNet Device” for information on setting
device attributes.
Editing IDNet Device Attributes
Editing Hardware Type
The hardware type identifies the specific device assigned to
the IDNet address. Table 4-1 and Table 4-2 identify the
required hardware types for all IDNet devices and modules.
1.
Follow the steps outlined in “Accessing IDNet Pro-
gramming Menus” earlier in this chapter. Select “Edit”
and then press <ENTER>. The display shows the first
point in the list. For example:
IDNet: 1
Pull
Lobby Door
2.
Use the <NEXT> and <PREV> keys to scroll through
the list of points until the appropriate point is displayed.
Press <ENTER>. A prompt similar to the following
appears.
IDNet: 1
F: [Hardware Type]
3.
Press <ENTER>. A prompt similar to the following
appears, allowing you to set the Hardware Type.
IDNet: 1
[ADRPUL]
4.
Use the <NEXT> and <PREV> keys to scroll through
the list of available Hardware Types. See the descrip-
tions in Table 4-1and Table 4-2 for more information.
Press <ENTER> when the applicable Hardware Type is
displayed. A prompt similar to the following appears,
asking you to confirm the operation.
<ENTER>= Confirm
[ADRPUL]
5.
<ENTER> will select the hardware type shown, while
<EXIT/CLEAR> will return to the previous screen
without making any changes
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...