Chapter 6. Manually Programming Annunciators
6-5
<ENTER>=Accept
Prg: [LED]
2.
Press <ENTER>. A scrollable list of points appears.
Use the <NEXT> and <PREV> keys to scroll to the
LED point you want to edit. The display appears similar
to the following.
LED Card 5, Pt 1
LED
1/24
3.
Press <ENTER>. The next prompt appears similar to
the following:
LED Card 5, Pt 1
Fn: [Edit Mode]
4.
Press <ENTER>. A prompt similar to the following
appears.
Mode Prg - Output
[TRBL]
15-10
5.
Use the <NEXT> and <PREV> keys to scroll through
the available modes. As you scroll through the modes,
the default reference address for the mode appears to the
right of the mode. Refer to Table 6-3 for a list of the
available modes.
6.
When the appropriate mode is selected, use the right
arrow key to move the cursor brackets over to the refer-
ence point. Press the <FUNCTION> key. This changes
the numerical designation of the reference point to a
text-based description. Refer to Table 6-4 for a list of
common reference points. For example:
Type: BZONE
Fire
IDC10
7.
Use the <NEXT> and <PREV> keys to scroll through
the list of available reference points.
8.
Press <ENTER> when the appropriate reference point is
displayed. The prompt shown in Step 4 reappears.
9.
Press <ENTER>. A prompt appears, asking you to con-
firm the changes.
10. Press <ENTER> to confirm the changes.
Table 6-3 LED Modes
Mode
Description
FIRE
Output activates when referenced
point is in an Alarm condition.
SUPV
Output activates when referenced
point is in a Supervisory condition.
TRBL
Output activates when referenced
point is in a Trouble condition.
DISA
Output activates when the refer-
enced point is Disabled.
ON
Output activates when the state of the
reference point is ON.
OFF
Output activates when the state of the
reference point is OFF.
LF
Output activates when any point is in an
alarm condition.
LS
Output activates when any point is in a
supervisory condition.
LT
Output activates when any point is in a
trouble condition.
Table 6-4 Common LED Reference Points
Reference
Point
Description
IDNet 1-200
Separate reference point for each
IDNet initiating device. State moni-
tored determined by selected LED
mode.
Aux Relays 1
and 2
Separate reference point for each
relay. State monitored determined
by selected LED mode.
City/DACT
Disconnect
Separate reference point (18-14) for dis-
connect and trouble. Typical use is to
monitor the ON state of either point.
City Trouble
Control
Bypass
Separate reference point for each type
of bypass.Typical use is to monitor the
ON state of any of the points.
Elevator
Bypass
Door Bypass
Table 6-3 LED Modes
Mode
Description
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...