Chapter 2. Installation/System Checkout
2-5
Class A/Class B NAC Wiring
The following guidelines and restrictions apply to notifica-
tion appliance circuits (NACs) located on either the main
system board (MSB) or on the Expansion Power Supply
(EPS).
•
All wiring to be 18 AWG (min.) to 12 AWG (max.).
•
Conductors must test free of all grounds and stray volt-
ages before connection to appliances and panel.
•
All wiring is supervised and power limited.
•
Wire Class A (Style Z) NACs from B+ and B- to each
appliance as shown. No EOL device is needed. Connect
wires from +/- terminals of the last appliance to the
A+/A- terminals as shown.
•
Voltage Rating: Refer to “NAC Ratings” on Page 2-7
for specific voltage specifications. Maximum ripple:
1/2 V peak-to-peak.
•
Current rating 2A max. for either circuit. 3A total
between both NAC circuits and AUX 24V load.
•
When using the following SimplexMulti-Candela appli-
ances, each NAC is rated for 2A max.
-
4906-9101
-
4906-9102
-
4906-9103
-
4906-9104
-
4906-9127
-
4906-9128
-
4906-9129
-
4906-9130
-
4906-9151
-
4906-9153
-
4906-9154
•
For all other UL-listed notification appliances, each
NAC is rated at 1.5A max.
•
Synchronization of strobes across all NACs in a system
is UL-listed for all of the above SimplexMulti-Candela
models, with a maximum of 34 appliances on a NAC
(15 Cd setting).
•
Terminal designations are for the alarm state (+/-).
•
If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Number
2081-9028 or 2081-9044. A protector must be installed
at each building exit/entrance. Each 2081-9028 adds .2
ohm wiring resistance. Each 2081-9044 adds 6 ohms
wiring resistance. Use of the 2081-9044 will signifi-
cantly reduce wiring distance.
•
System is shipped with 10K, 1/2W resistors connected
across NAC B+/B- for each circuit. Remove this resis-
tor from any circuits in use. Leave it installed if circuits
are unused.
•
Wiring chart gives maximum distance for 1/4 - 2 A
loads. For Class B circuits, wiring distance is from
panel terminals to last appliance. For Class A circuits,
wiring distance is from panel terminals to last appliance
and back to terminals. Use of Simplex Model 2081-
9044 will reduce the wire distance.
•
When using two-wire audible/visible appliances, maxi-
mum wiring capacitance of .22 uF must be considered.
•
Terminate Class B (Style Y) NACs as shown using Sim-
plex 733-894 (4081-9008) 10K 1/2 W resistor harness.
For Canadian applications, mount end-of-line resistor to
TEPG-US Model 431537 EOL plate in accordance with
ULC-S527.
•
The Expansion Power Supply (if used) mounts next to
the MSB. NAC wiring is routed within the cabinet as
shown below.
Maximum Wiring Distance in Feet
Alarm
Current
(Amps)
18
AWG
16
AWG
14
AWG
12
AWG
Line
Resistance
(Ohms)
.25
840
1335
2126
3382
12
.50
420
667
1063
1691
6
.75
280
445
709
1127
4
1.0
210
334
532
845
3
1.25
168
267
425
676
2.4
1.50
140
222
354
564
2
1.75
120
191
304
483
1.71
2.0
105
167
266
423
1.5
EPS
NACs
Main
System
Board
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...