Chapter 2. Installation/System Checkout
2-12
City Connect Module Wiring
•
City connect module mounts to the main system as
shown. Refer to City Module Installation Instructions
for details.
•
City module consists of two circuits that are jumper-
configured. Circuits may be configured for reverse-
polarity or local energy operation. See jumper setting
table for details. Modules must also be added to the sys-
tem configuration. See “System Options” later in this
manual.
•
All wiring to be per NFPA-72, NEC, and local codes.
Minimum 20 AWG for reverse polarity circuits; mini-
mum 18 AWG for local energy circuits.
•
Wiring is supervised for opens and grounds, but not
power-limited.
•
Conductors must test free of all grounds.
•
For specific information about reverse polarity and local
energy circuits see Figure 2-14.
•
If wiring is routed outside the building, use of a listed
secondary protector is required. Use Simplex Model
Number 2081-9044. A protector must be installed at
each location the wiring enters or exits a building. Each
2081-9044 adds 6 ohms wiring resistance and is rated
for 200 mA. Maximum wiring resistance is reduced by
6 ohms for each 2081-9044 used.
•
Circuits are shipped with 3.3K, 1/2W resistor installed.
Remove resistor before wiring circuit. Leave installed
on unused circuits.
Figure 2-14 City Connect Module Wiring
TB1
DANGER
HIGH VOLTAGE
IN THIS AREA
DACT TELEPHONE
CONNECTIONS
CITY CONNECT
MODULE
CITY CONNECT
MODULE
P6
1
2
3
4
CKT 1
CKT 2
SEE DETAIL A
P6 SELECTS CITY CIRCUIT 2 OPERATION.
POS. 1 - 2 AND 3 - 4 FOR CITY 2 TO
ACTIVATE ON SUPERVISORY CONDITION
REVERSE POLARITY
LOCAL ENERGY
15mA MAX. AT 24VDC
24V DC NORMAL
4mA SUPERVISION CURRENT
500mA MAX. ALARM CURRENT (PULSED)
INTENDED FOR CONNECTION TO A POLARITY
REVERSAL CIRCUIT OF A REMOTE STATION
RECEIVING UNIT HAVING COMPATIBLE RATINGS
20 . 4V - 28VDC, 1/2 p - p RIPPLE (MAX.)
INTENDED FOR CONNECTION TO A 14 . 5 OHM
TRIP COIL.
MAXIMUM WIRING RESISTANCE: 4000 OHMS
WITH 2200 OHM TRIP COIL (6200 OHM TOTAL)
POLARITY MARKED ON TERMINALS REFLECTS
THE ALARM STATE.
POS. 1 - 3 FOR CITY 2 TO
ACTIVATE ON TROUBLE CONDITION
DETAIL A
TB2
3A
FUSE
SW
SW
1
2
3
4
3A
FUSE
3A
FUSE
3A
FUSE
P3
P6
1
2
3
4
P6
1
2
3
4
LE
RP
LE
RP
LE
RP
LE
RP
P2
P4
P5
SW
SW
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
5
1
2
3
4
5
6
7
8
TB3
MAIN SYSTEM BOARD - ADDRESSABLE (MSB - A)
JUMPER POSITIONS
CITY 1
P3: 1 - 2, 3 - 4, 5 - 6
P2: 2 - 3
P5: 1 - 2, 3 - 4, 5 - 6
P4: 2 - 3
P3: 7 - 8, 9 - 10
P2: 1 - 2
P5: 7 - 8, 9 - 10
P4: 1 - 2
REVERSE POLARITY
LOCAL ENERGY
CITY 2
P5
LE
RP
LE
RP
P4
10
9
8
7
6
5
4
3
2
1
P3
LE
RP
LE
RP
P2
10
9
8
7
6
5
4
3
2
1
Employ a 14.5 Ohm Trip Coil
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...