Chapter 4. Manually Programming IDNet Points
4-4
Edit IDNet Function Type
The panel’s addressable channel supports the following
function types.
•
Input function types
are used with monitor points.
The function type determines the way in which the
panel responds to a change in a point’s electrical state.
For example, when you assign the SMOKE function
type to a smoke detector, the system interprets an open
on the device as a trouble and a short/abnormal state as
a fire. Refer to Table 4-3 for a list of input function
types and states.
•
Output Function Types
are used with
notification
appliances and relays (connected via a 4090-9007 Sig-
nal IAM). An output point’s function type determines
the operation of the NAC or relay (e.g., on til silence; on
til reset, etc.) Refer to Table 4-4 for a list of output func-
tion types. Notification appliances and relays controlled
via a 4090-9007 Signal IAM or 4090-9002 Relay IAM
activate with a steady output; coding of notification
appliances and relays attached to IAMs is not allowed.
Program the input and output function types as follows:
1.
Follow the steps outlined in “Accessing IDNet Pro-
gramming Menus” earlier in this chapter. Select “Edit”
and then press <ENTER>. The display shows the first
point in the list. For example:
IDNet: 1
Pull
Lobby Door
2.
Use the <NEXT> and <PREV> keys to scroll through
the list of points until the appropriate point is displayed.
Press <ENTER>. A prompt similar to the following
appears.
IDNet: 1
F: [Hardware Type]
3.
Use the <NEXT> and <PREV> keys to scroll through
the options until [Function] is displayed and then press
ENTER. A prompt similar to the following appears,
allowing you to select the applicable function.
IDNet: 1
[PULL]
4.
Use the <NEXT> and <PREV> keys to scroll through
the list of available function types. The list of displayed
function types depends on the hardware type assigned to
the point.
5.
Press <ENTER> when the appropriate function type is
shown. The system prompts you to confirm the selec-
tion.
<ENTER>= Confirm
[PULL]
6.
<ENTER> will select the function in the display, while
<EXIT/CLEAR> will return to the previous screen
without making any changes
Note: Refer to table at top of Page 4-1 for UL 864 compliant
options.
4090-9116
Addressable Isolator
ISOL
4090-9101
Class B Zone Addressable Module for monitor
devices
MBZAM
4090-9106
Class A Zone Addressable Module (ZAM) for
monitor devices
MAZAM
4099-9010 Single action pull station
4099-9012 Dual Action (Push/Pull)
Addressable Pull Stations
ADRPUL
Table 4-2 Hardware Types, IDNet Modules
Module
Use this
Hardware
Type
Table 4-3 Input Function Types
Function
Type
Device State = Status
SMOKE
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with smoke detectors.
HEAT
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with heat detectors.
PULL
Normal = NORMAL
Current-Limited = FIRE
Short = FIRE
Open = TROUBLE
Use with pull stations.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...