Chapter 6. Manually Programming Annunciators
6-2
Adding an Annunciator
Automatically Adding Annunciator Cards
Use the Automatic Programming option to automatically
add annunciator modules to the job. (This option will also
detect and add an Expansion Power Supply and City Card, if
installed.)
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Automatic Programming] option is displayed.
Press <ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press <ENTER>. The following prompt appears.
<ENTER>=Accept
AP: [Reconfig All]
3.
Use the <NEXT> key to select [Detect New]. The fol-
lowing prompt appears.
<ENTER> to Continue
*May CHANGE Setting*
4.
Press <ENTER> to detect and add annunciators to the
job.
Manually Adding an Annunciator Module
Use the following procedure to manually add the annuncia-
tor module to the job.
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press Enter. The Programming menu appears:
<ENTER>=Accept
Prg:[Points]
3.
Use the <NEXT> and <PREV> keys to scroll through
the choices until “Annuns” is displayed.
<ENTER>=Accept
Prg: [Annuns]
4.
Press <ENTER>. Use the <NEXT> and <PREV> keys
to scroll through the choices until “Add” is displayed.
<ENTER>=Accept
Annuns: [Add]
5.
Press <ENTER>. A prompt appears, asking you to iden-
tify the specific type of annunciator.
<ENTER>=Accept
Add: [LCD]
6.
Use the <NEXT> and <PREV> keys to select one of the
following:
•
Zone Ann
•
Remote LED/SW
•
LCD. Option not applicable to this panel.
7.
Press <ENTER>. A prompt appears, asking you to set
the card address for the annunciator. The address you
specify must match the address set via dip switch on the
annunciator. The address must be in the range of 4
through 7.
8.
Use the <NEXT> and <PREV> keys to select the
appropriate address and press ENTER.
9.
A prompt appears asking you to confirm the addition of
the annunciator. Pressing <ENTER> will accept any
changes made and exit. Use the <EXIT/CLEAR> key to
quit without saving.
Accessing Annunciator Menus
1.
Press the <MENU> key. Press <NEXT> or <PREV>
until the [Programming] option is displayed. Press
<ENTER>. The following displays:
FIRE ALARM
SUSPENDED
<ENTER> to Program
<EXIT> to resume
2.
Press <ENTER>. The Programming menu appears.
[Points] is the default selection, which allows you to
make changes to a specific point’s programming.
<ENTER>=Accept
Prg:[Points]
3.
Press <ENTER>. A prompt appears, allowing you to
select the type of point to manually edit. By default,
[IDC] is the first choice.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for TrueAlarm 4008- 9121
Page 1: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 6: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 10: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 34: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 58: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 68: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 72: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 80: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 85: ...Technical Manuals Online http www tech man com firealarmresources com...
Page 86: ...Technical Manuals Online http www tech man com firealarmresources com...