AUTOCALL TFX Fire Control System Operator’s Manual

26

the control panel to recognize the alarm. Approximately 10 seconds later, the panel will reset the

zone of conventional detectors for 45 seconds. During this time, make sure the tested detector is

clear of smoke, then proceed to test the next detector.

The panel will increment the LCD display counter for each recorded detector activation.

Solo Test Sounders ------

This function allows signalling appliances to be tested without first raising an alarm. It is possible

to test either ALL the signalling appliances, or the signalling appliances in

one

zone only. Proceed as follows:

1. Select the “Solo Test Sounders”option from the Test System menu. The display will respond with the

following message:

Zone no:

(Yes=all)

A blinking cursor indicates that an operator input is required. Entering zone “0”will cause only the common

indicating appliances to be tested.

2. Enter the number of the required zone and press

YES/ENTER

.

3. The display will respond with the following message:

sounders in

Solo test

exit with quit

All signalling appliances (in the selected zone) will operate for approximately 2 seconds every 30 seconds.

4. Walk around the site to all indicating appliances. Check for correct operation of the indicating

appliances.

5. When all the indicating appliances have been checked, press

QUIT

. The display will respond with

the following message:

Solo test terminated

6. The Solo test function will automatically terminate one hour after the solo test is completed, if not ter-

minated manually. If an alarm occurs during the solo test, the function will be automatically terminated

and the AUTOCALL TFX-500M/800M panel will respond as described in Section 1.1, “Quick

Response------Alarm.”

3.7. Isolate Menu

This menu selection allows for devices to be isolated so they do not respond to an alarm. Zones and points may be

temporarily isolated (taken out of service) for many reasons------device repair, circuit repair, etc. Only Customer Manager

status levels and above may access these menu options.

Figure 3--7 Isolate menu options sequence.

s

s

t

Y

N or

t

Y

N or

Y

Next Menu

Do you want to

isolate points?

isolate zone?

(sensors only)

isolate point?

(adr. loop only)

Do you want to

de--isolate pts?

Zonal isolation

Point isolation

Note: When system points are isolated, the SYSTEM TROUBLE LED and ZONE

TROUBLE LED related to the isolated point(s) are lighted continuously and the front

panel buzzer will sound intermittently.

firealarmresources.com

Summary of Contents for TFX-500M

Page 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...

Page 2: ...This page is blank firealarmresources com...

Page 3: ...IONAL LTD COMPANY 835 Sharon Drive Westlake Ohio 44145 G i AUTOCALL TFX 500M and TFX 800M Fire Control System Operator s Manual Publication Number 850516 Issue 3 Revision A September 1997 firealarmres...

Page 4: ...hority having jurisdiction For further information contact AUTOCALL TFX Products 835 Sharon Drive Westlake Ohio 44145 Telephone 440 871 9900 Facsimile 440 871 8320 WARNING This equipment generates and...

Page 5: ...TFX 500M and TFX 800M AUTOCALL TFX 500 and TFX 800 CONSYSrProgramming Guide Publication Number 850463 Programming the TFX Fire Control System via a personal computer only authorized and trained person...

Page 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...

Page 7: ...ormal Operation 13 2 3 1 Access Levels 14 2 3 2 Initial Condition 14 2 3 3 Event Monitoring 14 2 4 Multiple Events 16 2 4 1 Event Priority 16 2 4 2 Alarm Resound Always Option 16 2 4 3 Bell Map Alarm...

Page 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...

Page 9: ...tting and operating the AUTOCALL TFX 500M and AUTOCALL TFX 800M fire alarm system requires the use of the special key Make sure you have one available Only authorized personnel may reset a fire contro...

Page 10: ...NE TROUBLE LED yellow O KEYSWITCH F ALPHANUMERIC DISPLAY P PANEL SILENCE touch button G NO DELETE touch button Q ALARM SILENCE touch button H SCROLL UP touch button R SYSTEM RESET touch button I SCROL...

Page 11: ...ARM LED red K POWER LED green B TROUBLE LED yellow L QUIT touch button C SUPERVISORY LED yellow M FAST ACCESS touch button D ZONE ALARM LED red N NUMERIC touch pad E ZONE TROUBLE LED yellow O KEYSWITC...

Page 12: ...u do What happens Look at the AUTOCALL TFX 500M 800M control panels to see Alarms Listen for Alarm signals 1 Two red FIRE ALARM LEDs light 2 Red ZONE ALARM LED s flash 3 Buzzer sounds 4 Alarm bells ho...

Page 13: ...panels to see SUPERVISORY lights and messages Listen for SUPERVISORY signals 1 Yellow SUPERVISORY LED light 2 Buzzer sounds a pulsing tone 3 Display gives SUPERVISORY message Read the display to deter...

Page 14: ...ROUBLE lights and messages Listen for TROUBLE signals 1 Yellow TROUBLE LED light 2 Yellow ZONE TROUBLE LED s light 2 Buzzer sounds a pulsing tone 3 Display gives TROUBLE message Read the display to de...

Page 15: ...TOR DISPLAY MODULE QUIT 23 JAN 94 22 17 02 1 Enter your passcode number or use Special Passcode 0911 and press YES ENTER The display will respond with the following message Do you want to accept event...

Page 16: ...12 o clock position Allows access to touchpad functions Press ALARM SILENCE 1 Buzzer will change from constant to pulsing tone for alarm change from pulsing to off for trouble or supervisory alarm al...

Page 17: ...p Zone 2 A48 001 FIRST SILENCE ALARMS RESET SYSTEM To reset the system 1 Accept events 2 Insert the key and turn the keyswitch to Enable 12 o clock position position 3 Press ALARM SILENCE to silence t...

Page 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...

Page 19: ...follows Figure 2 1 AUTOCALL TFX 500M 800M Keyswitch Positions Key FIRE TROUBLE SUPERVISORY POWER PANEL SILENCE ALARM SILENCE SYSTEM RESET DRILL ENABLE OFF LAMP TEST TURN CLOCKWISE TO 12 O CLOCK POSITI...

Page 20: ...is pressed RESET Pressing RESET while the keyswitch is in the Enable position resets the system following the occurrence of an alarm or other event The system can only be reset after the signalling d...

Page 21: ...LL TFX 500M 800M control panel to be operated from a remote location The front panel of the Remote Ops Dis panel is identical to that of the AUTOCALL TFX 500M 800M see Figure 1 2 or 1 3 It shows the s...

Page 22: ...s 0001 to 9999 2 3 2 Initial Condition At initial power up the AUTOCALL TFX 500M 800M display shows the following message until the power up sequence is completed TFX 500 or TFX 800 initialising initi...

Page 23: ...ed in the order of priority Event priority is as follows 1 FIRE EVACUATE 6 FAULTS ADDRESSABLE POINTS 2 FIRE ALERT 7 FAULTS CLEAR 3 WARNINGS 8 RESET SILENCE 4 FAULTS SYSTEM 9 PRINTER OFF LINE 5 SUPERVI...

Page 24: ...the following will occur a Outstanding Events counter will be incremented b Signalling appliances will not be reactivated 3 If the bells horns strobes signalling appliances HAVE been silenced and the...

Page 25: ...there are no other troubles or events the system will return to the normal or Standby mode The display will return to the normal date time display NOTE Alarms override trouble conditions Any trouble c...

Page 26: ...el to remain in a Trouble condition The fire control system may not respond properly to a fire alarm condition Contact yourl Fire Protection Systems representative or Technical Services 835 Sharon Dri...

Page 27: ...data Print Menu s Open VFP Available only at Cus tomer Manager access level and above Other options not shown are available at higher access levels Virtual Front Panel Menu Only available on ThornNet...

Page 28: ...uence s Y Next Menu View Unrestored Events t Y Do you want to view log N or Events Display or No Events Found If there are unrestored events in the system the display will show the event s in the foll...

Page 29: ...d in order of priority the highest priority first Press t to move forward through the log Press s to move backward through the log When either the beginning OR end of the log is reached an End of Log...

Page 30: ...he zones may be viewed A 1 indicates that a zone or a point in the zone IS isolated a 0 indicates that it is not Thus for the example given below all or part of zones 1 and 16 are isolated Pressing QU...

Page 31: ...ay be set Proceed as follows 1 Select the Set Time option The display will respond with the following message Enter time as HHMMSS In this display HH Hours MM Minutes SS Seconds The cursor will blink...

Page 32: ...want to test system Do you want to sounders Do you want to isolate points t Y N or s Point solo test zone Zonal solo test Solo test Point solo test Solo test Sounder solo test Note During Solo Test S...

Page 33: ...ontact monitor modules or detector monitor modules to be tested without raising an alarm Warning This function will disable the point s under test 1 Select the Solo Test Point option from the menu The...

Page 34: ...ly 2 seconds every 30 seconds 4 Walk around the site to all indicating appliances Check for correct operation of the indicating appliances 5 When all the indicating appliances have been checked press...

Page 35: ...mple Zone 1 has been isolated POINT ISOLATED 3rd Floor 12 15 00 23 Jan 90 Non Addressable Pnt Zone 1 Isolate Point 2 Way Data Circuits Only Individual devices may be isolated using their addresses Pro...

Page 36: ...menu options sequence shown in Figure 3 8 will be displayed Figure 3 8 De Isolate menu options sequence s s t Y N or t Y N or Y Next Menu Do you want to de isolate pnts de isolate zone sensors only de...

Page 37: ...ETE The display will return to that shown in Step 1 above 8 Once the correct loop has been chosen the display will respond with the following message Point no 0 none Yes all 9 Enter the address of the...

Page 38: ...s in this menu allow the contents of the Event Log or the results of a Solo Test to be printed Figure 3 10 Print Data menu options sequence s s t Y N or t Y N or Y Do you want to print data Print poin...

Page 39: ...in the summary table contain the following parameters Table 3 2 Printer message parameters and abbreviations Abbreviation Parameter Address Zone loop and point number Dev Device type code number Con...

Page 40: ...ation point type number The MAXIMUM number of events that the log can hold is 150 Asking for more than this number will cause the AUTOCALL TFX 500M 800M control panel to display invalid try again 5 Th...

Page 41: ...eceived attention Periodic System Checks The system can be configured to display a warning message accompanied by an audible alert when the system test is due This feature must be configured by an aut...

Page 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...

Page 43: ...This page is blank firealarmresources com...

Page 44: ...rinted in the U S A Specifications and other information shown were current as of publication and are subject to change without notice 2001 Simplex Time Recorder Co 850 516 Rev A firealarmresources co...

Reviews: