AUTOCALL TFX Fire Control System Operator’s Manual
26
the control panel to recognize the alarm. Approximately 10 seconds later, the panel will reset the
zone of conventional detectors for 45 seconds. During this time, make sure the tested detector is
clear of smoke, then proceed to test the next detector.
The panel will increment the LCD display counter for each recorded detector activation.
Solo Test Sounders ------
This function allows signalling appliances to be tested without first raising an alarm. It is possible
to test either ALL the signalling appliances, or the signalling appliances in
one
zone only. Proceed as follows:
1. Select the “Solo Test Sounders”option from the Test System menu. The display will respond with the
following message:
Zone no:
(Yes=all)
A blinking cursor indicates that an operator input is required. Entering zone “0”will cause only the common
indicating appliances to be tested.
2. Enter the number of the required zone and press
YES/ENTER
.
3. The display will respond with the following message:
sounders in
Solo test
exit with quit
All signalling appliances (in the selected zone) will operate for approximately 2 seconds every 30 seconds.
4. Walk around the site to all indicating appliances. Check for correct operation of the indicating
appliances.
5. When all the indicating appliances have been checked, press
QUIT
. The display will respond with
the following message:
Solo test terminated
6. The Solo test function will automatically terminate one hour after the solo test is completed, if not ter-
minated manually. If an alarm occurs during the solo test, the function will be automatically terminated
and the AUTOCALL TFX-500M/800M panel will respond as described in Section 1.1, “Quick
Response------Alarm.”
3.7. Isolate Menu
This menu selection allows for devices to be isolated so they do not respond to an alarm. Zones and points may be
temporarily isolated (taken out of service) for many reasons------device repair, circuit repair, etc. Only Customer Manager
status levels and above may access these menu options.
Figure 3--7 Isolate menu options sequence.
s
s
t
Y
N or
t
Y
N or
Y
Next Menu
Do you want to
isolate points?
isolate zone?
(sensors only)
isolate point?
(adr. loop only)
Do you want to
de--isolate pts?
Zonal isolation
Point isolation
Note: When system points are isolated, the SYSTEM TROUBLE LED and ZONE
TROUBLE LED related to the isolated point(s) are lighted continuously and the front
panel buzzer will sound intermittently.
firealarmresources.com
Summary of Contents for TFX-500M
Page 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...
Page 2: ...This page is blank firealarmresources com...
Page 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...
Page 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...
Page 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...
Page 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...