7
1.4. Quick Response— Accept (Acknowledge) Alarms
Before you silence the alarms or reset the system, you should “accept”(acknowledge) the event at the control panel.
Figure 1--7 Enter your Access Code or use Special Passcode (for example, 0911) at touch-pad for
Event Acceptance prompt.
FIRE
TROUBLE
SUPERVISORY
POWER
PANEL SILENCE
ALARM SILENCE
SYSTEM RESET
DRILL
ENABLE
OFF
LAMP
TEST
1
2
3
4
5
6
7
8
9
0
NO
YES
DELETE ENTER
FAST
ACCESS
B
Y
OPERATOR DISPLAY MODULE
QUIT
23 JAN 94 22:17:02
1. Enter your passcode number or use Special Passcode (0911) and press
YES/ENTER
The display
will respond with the following message:
Do you want to
accept events?
2. Press
YES/ENTER
again. The display will then show a message that looks like this example:
FIRE ALARM
Main Workshop
Zone 4 A48 001
accept (Y/N)?
3. Press
YES/ENTER
to accept the event. The display will say:
event accepted.
If the event dis-
played is NOT to be accepted, press
NO/DELETE
and the display will show the next event (if any).
Pressing
t
or
s
will move the display through all the outstanding (unaccepted) events.
firealarmresources.com
Summary of Contents for TFX-500M
Page 1: ...TFX 500M TFX 800M Fire Control System A U T O C A L L Operator s Manual firealarmresources com...
Page 2: ...This page is blank firealarmresources com...
Page 6: ...AUTOCALL TFX System Operator s Manual iv firealarmresources com...
Page 8: ...AUTOCALL TFX System Operator s Manual vi firealarmresources com...
Page 18: ...AUTOCALL TFX Fire Control System Operator s Manual 10 firealarmresources com...
Page 42: ...AUTOCALL TFX Fire Control System Operator s Manual 34 firealarmresources com...