9
In either a 4100 or a 4120 system, the SafeLINC FPII takes up two 2-inch slots. Secure the
assembly to the mounting rails as shown below.
Mount the card to the left-most position on the mounting rails (if possible).
IMPORTANT:
The 637-591 Bracket must be mounted to the 4100/4120 mounting rails
before the SafeLINC FPII card is mounted.
Figure 5. 4100/4120 Mounting
Mounting the SafeLINC FPII Card,
Continued
4100/4120 Mounting
637-591 Bracket must be
mounted to rails first
SafeLINC FPII
Card
#6 Screws
Washers