26
The SafeLINC FPII card must be connected to a PC to configure the basic settings. The PC must
meet the requirements of UL-Listed Information Technology Equipment.
Use Download Cable 733-794 to connect P9 on the SafeLINC FPII card to the PC.
•
Align red stripe on Download Cable with Pin 1 on P9.
Figure 24. Connecting SafeLINC FPII Card to PC
Hyperterm is a terminal emulation program available under all Windows platforms.
Configure the Hyperterm or equivalent Terminal Emulation program to run at 19.2K, 8-N-1 with
no hardware handshaking. Under settings, configure emulation to Auto Select.
Note:
Some users may experience difficulties with Auto Select. If you are one of these users,
please change to VT-100 emulation.
Before you configure the SafeLINC FPII on the boot prompt, you need to check out if the MIS/IT
configured IP address for where you intend to install the SafeLINC FPII is active on the network.
Since the SafeLINC FPII is not yet operational at this point, you should not be able to successfully
communicate with the assigned IP address. To perform this check, you will use a Windows Utility
called Ping.
•
Open a DOS Window on any PC connected to same LAN as the SafeLINC FPII.
•
At the DOS Prompt, type in:
ping
ip_address
Substitute the
ip_address
parameter for the actual IP Address assigned by the MIS/IT
Department for the SafeLINC FPII. For example, ping 192.168.0.1 and press Enter.
C:\>ping 192.168.0.1
Pinging 192.168.0.1 with 32 bytes of data:
Request timed out.
Request timed out.
Request timed out.
Request timed out.
Ping statistics for 192.168.0.1:
Packets: Sent = 4, Received = 0, Lost = 4 (100% loss),
Approximate round trip times in milli-seconds:
Minimum = 0ms, Maximum = 0ms, Average = 0ms
C:\>
Figure 25. Expected Results (No Device Response to Ping Command)
Continued on next page
Connecting a PC to the SafeLINC FPII Diagnostic & Configuration Port
Connecting
SafeLINC FPII Card
to a PC
Configuring a
Terminal Emulation
Program
Checking for
Duplicate IP
Addresses
733-794
P9
PC or
LAPTOP
SafeLINC
FPII
Summary of Contents for SafeLINC 4020-0160
Page 2: ......
Page 55: ...49 MIS IT Configuration Worksheet...
Page 56: ...50 MIS IT Configuration Worksheet Continued...
Page 57: ......