The SafeLINC FPII card can connect to a 4020 as shown in Figure 9. This illustration shows the
SafeLINC FPII card connected to MAPNET Interface Board via Harness 733-693 and the 4020
Power & Comms Connector P2. This is an example of one connection to the 4020. If the
MAPNET Interface Board is unavailable for power and communications, you will need to connect
to another 4020 board. Instead of the MAPNET Interface Board, you also can connect Harness
733-693 from the SafeLINC FPII’s P2 connector to the Standard Slave Card (P6, P7), Power
Supply Interface Board (P2, P3), 8-Point I/O Board (P9, P10), 2120/RS232 Interface Board (P8,
P9), or Network Option Board/Repeater Card (P11, P12). See the 4020 Interconnection Diagrams
(841-906) for more information.
TB1
P2
P1
P3
MAPNET INTERFACE BD
565-241
OR
2120/RS232
INTERFACE BD
565-224
OR
NETWORK OPTION BD/
REPEATER CARD
565-411 OR -518
OR
CONTACT CLOSURE
DACT 742-015
OR
PHYSICAL BRIDGE MODEM
MODULE STYLE 4
636-765
OR
SDACT
742-059
Figure 9. 4020-Style Wiring
SafeLINC FPII Field Wiring,
Continued
4020-Style Wiring
4020 Power & Comms
Connector P2
Power &
Comms
Harness
733-693
P9:
SafeLINC FPII Diagnostic
and Configuration Port (Not
Connected During Normal
Operation)
Use 733-794 Download
Cable to Interface SafeLINC
FPII to PC/Laptop.
J1:
Connect to Corporate LAN. All equipment
comprising Corporate LAN is to be UL-Listed
Information Technology Equipment.
Use EIA/TIA-568a CAT-5-Compliant Cable,
or better.
Either Unshielded (UTP) or Shielded (STP)
Cable is Acceptable.
Terminate Cable with RJ-45 Connector (if
not already terminated by MIS/IT).