This section describes how to configure the SafeLINC FPII card using DIP switches and jumpers.
DIP switch SW2 is used to set the SafeLINC FPII card’s communications to either 4020/RUI-
Style, 4100/4120 Legacy, or 4100U/4100ES/4010ES-Style communications. Set the DIP switch
according to the illustration.
IMPORTANT:
For proper communications, recheck the SW2 settings before applying
power.
FigureTag FD9-349-01
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
Figure 2. SW2 Switch Settings
Use
P10, P11,
P14
and
P15
to set the SafeLINC FPII card’s incoming protocol. Verify that
P10,
P11,
P14
and
P15
are all set to Positions 1 and 2. You should not have to change the positions
because they are set to Positions 1 and 2 by default from the factory.
P10, P11, P14, P15:
Positions 1-2: CPP (default from factory).
1 2 3 Positions 2-3: Reserved for future use.
Configuring the SafeLINC FPII Card
Overview
Setting
Communications
Setting Computer
Port Protocol (CPP)
Functionality
ON
OFF
ON
OFF
4020/RUI-Style
Communications:
4100/4120 Legacy
Communications:
1 2 3
ON
OFF
4100U/4010ES-Style
Communications: