25
14.
Click the Port Vectoring tab and then highlight the RS232 card (not the Service Port
selection).
Figure 23. Event Reporting Option (4100U software shown)
15.
As shown in Figure 23, enable the Fire Alarm, Trouble, Supervisory, and Priority 2 Alarm
Events as well as System Reset and Alarm Silence by checking off the field next to each event
type. Leave the remaining event types disabled.
16.
Save the job or continue to build the job as necessary. The SafeLINC FPII configuration
portion is now complete.
Adding the SafeLINC FPII to the FACP via the Programmer,
Continued
Using the
Windows-Based
Programmer