Document: LT0400
4100U-S1 Programming Guide
Appendices
Issue 1.4
15 December 2010
Page 12-17
12.4.2
Lists
Zone 1
L261
– Zone 1 Alarm List
L262
– Zone 2 Alarm List
…
L260+n
– Zone n Alarm List
12.4.3
Switches and LEDs
Zone 1
3-65
– Zone 1 Multifunction Switch
3-1
– Zone 1 Alarm LED
3-2
– Zone 1 Isolated LED
12.4.4
Zone 1 Equations
4-2 ZONE 1 Isolate Switch
[INPUTS]
STATUS
ON
P901 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 1
AND
NOT
STATUS
ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
AND
NOT
STATUS
ON
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
AND
RECALL
8
[END INPUTS]
[OUTPUTS]
HOLD
ON
PRI
=
9
,
9
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
HOLD
ON
PRI
=
9
,
9
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
[END OUTPUTS]
4-3 ZONE 1 De-Isolate Switch
[INPUTS]
STATUS
ON
P901 | DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 1
AND
STATUS
ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
AND
NOT
STATUS
ON
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
AND
RECALL
8
[END INPUTS]
[OUTPUTS]
HOLD
OFF
PRI
=
9
,
9
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
HOLD
ON
PRI
=
9
,
9
P701 | DIGITAL | UTILITY | ISOLATE TOGGLE ZONE 1
[END OUTPUTS]
4-4 ZONE 1 Isolate Stops Fire
[INPUTS]
STATUS
FIRE
L261 | LIST | MIXED | ALARM LIST ZONE 1
AND
NOT
STATUS
ON
P601 | DIGITAL | SUPERV | ISOLATE ZONE 1
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
P801 | DIGITAL | UTILITY | ALARM ZONE 1
[END OUTPUTS]