Document: LT0400
4100U-S1 Programming Guide
Adding Expansion Modules
Issue 1.4
15 December 2010
Page 8-7
8.4 Adding 4100-5004 8 Point Monitor Card.
The 4100-5004 8 Point Monitor Card provides eight conventional detector or contact closure
inputs. There are no restrictions on point types.
To add the 4100-5004 8 Point Monitor Card to the panel:
Select the
HARDWARE
Tab.
Expand the
Unit 0
, „Box 1‟
and
„Bay 2‟.
Click on the “
+
” sign beside
the
MONITOR
option on the
Available Hardware
window.
Drag and drop the
4100-
5004/5005 8 Point Class B
Sec Monitor
Icon over to the
Bay 2
icon.
The card will be added to the panel
configuration.
Double click on the card and in the
Properties
Tab,
select the card‟s
address and enter in the
Card
Custom Label:
text box, a
descriptive label.
Click the
Point Editing
tab and
add/edit the points‟ point types and
names. Record the point
addresses, as they are used within
user defined Custom Control
equations as in the following
example for ZN1 and SIG9.
When ZN1 is in ALARM,
operate SIG9.
[INPUTS]
STATUS
FIRE
ZN1
| SMONB | FIRE | MONITOR
CARD 7 ZONE ZN1
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
SIG9
| SIGB | SSIGNAL | SIGNAL
CARD 5 CIRCUIT SIG9
[END OUTPUTS]