Document: LT0400
4100U-S1 Programming Guide
Adding Expansion Modules
Issue 1.4
15 December 2010
Page 8-3
Click on the “
+
” sign beside the
INTERFACE
option on the
Available Hardware
window.
Drag and drop the
4100-3101
–
IDNET 250 Points
Icon on to the
Bay 2
icon.
An IDNET card will be added to
the panel configuration.
Block H
represents the location
in the bay, but this is not relevant
for the 4100U-S1.
[004]
is the address of the card
and MUST match the physical
address on the IDNET module.
WARNING: Use Address 5 or
higher.
4100-3101-IDNET 250 Points
is
the type of the card.
Now that the new IDNet card has been added, the addressable devices connected to this card can be
added to the panel configuration as follows:
Select the
Point Editing
Tab.