Document: LT0400
4100U-S1 Programming Guide
Appendices
Issue 1.4
15 December 2010
Page 12-11
3-14 Alarm and Fault Test Mode OFF
[INPUTS]
STATUS
ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND
STATUS
ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD
OFF
PRI
=
9
,
9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD
OFF
PRI
=
9
,
9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD
OFF
PRI
=
9
,
9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
PANEL
"ALARM and FAULT TEST OFF"
HOLD
OFF
PRI
=
7
,
7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-15 Alarm and Fault Test Timer
[INPUTS]
STATUS
ON
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
AND
NOT
STATUS
ON
L258 | LIST | DPSEUDO | ALARM TEST LIST
AND
NOT
STATUS
ON
L259 | LIST | DPSEUDO | FAULT TEST LIST
DELAY
CONSTANT
60
A257 | Analog Timer | ANALOG | TIMER | ALARM and FAULT TEST TIMEOUT
[END INPUTS]
[OUTPUTS]
HOLD
OFF
PRI
=
9
,
9
P514 | DIGITAL | UTILITY | ALARM TEST
HOLD
OFF
PRI
=
9
,
9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD
OFF
PRI
=
9
,
9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD
OFF
PRI
=
7
,
7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-16 Reset Alarm and Fault Test
INPUTS]
STATUS
ON
L258 | LIST | DPSEUDO | ALARM TEST LIST
AND
NOT
STATUS
ON
P514 | DIGITAL | UTILITY | ALARM TEST
SAVE
1
STATUS
ON
L259 | LIST | DPSEUDO | FAULT TEST LIST
AND
NOT
STATUS
ON
P515 | DIGITAL | UTILITY | FAULT TEST
OR
RECALL
1
OR
STATUS
ON
P0 | DIGITAL | UTILITY | SYSTEM RESET KEY
OR
STATUS
ON
P210 | DIGITAL | UTILITY | NETWORK DETECTOR RESET
OR
STATUS
ON
P212 | DIGITAL | UTILITY | DETECTOR/SYSTEM RESET
[END INPUTS]
[OUTPUTS]
HOLD
OFF
PRI
=
9
,
9
L258 | LIST | DPSEUDO | ALARM TEST LIST
HOLD
OFF
PRI
=
9
,
9
L259 | LIST | DPSEUDO | FAULT TEST LIST
[END OUTPUTS]