Document: LT0400
4100U-S1 Programming Guide
Appendices
Issue 1.4
15 December 2010
Page 12-5
12.2.5
Battery Test
The battery is automatically tested at 8:00:03 every Tuesday morning according to the
internal clock. The test runs for 1 hour (plus 5 seconds).
The battery test is disabled if any Alarm is present or an Alarm occurs during the battery test.
Manual battery tests can be started by activating P520.
References:
Point Address:
1-10 Battery Test Point
A256 Battery Test Timer
P520 Manual Battery Test
Equation:
3-8 Battery Test
[INPUTS]
WHEN
DAY
IS
TUE
AND
IF
ANALOG
=
CONSTANT
8
CNTS
A6 | Compare Analog | ANALOG | ANALOG | CURRENT HOUR
AND
IF
ANALOG
=
CONSTANT
0
CNTS
A7 | Compare Analog | ANALOG | ANALOG | CURRENT MINUTE
AND
IF
ANALOG
<=
CONSTANT
3
CNTS
A8 | Compare Analog | ANALOG | ANALOG | CURRENT SECOND
OR
STATUS
ON
P520 | DIGITAL | UTILITY | MANUAL BATTERY TEST CONTROL
AND
NOT
STATUS
ON
L257 | LIST | DPSEUDO | GENERAL FIRE TRIP LIST (ACF ISOLATABLE)
DELAY
CONSTANT
3605
A256 | Analog Timer | ANALOG | TIMER | BATTERY TEST TIMER
SAVE
1
IF
ANALOG
>
CONSTANT
0
CNTS
A256 | Compare Analog | ANALOG | TIMER | BATTERY TEST TIMER
AND
NOT
STATUS
ON
A256 | ANALOG | TIMER | BATTERY TEST TIMER
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
8
,
8
1
-
10
| SPECOUT | SPECOUT | CITY PRI2
TRACK
ON
PRI
=
9
,
9
P520 | DIGITAL | UTILITY | MANUAL BATTERY TEST CONTROL
[END OUTPUTS]
12.2.6
Alarm Verification Timing and Start Up settings
This equation is used to set any default settings when the panel is powered up or has been
restarted by CPU hardware reset button.
References:
Point Address:
A34 System Start up Pulse timer
A37 AVF Retard Time
A38 AVF Reset Time
A39 AVF Confirmation Time
P21 Disable Program 5 Custom Control for Alarm and Fault Test
P478 Inhibits device trouble when the device is disabled
Equations: