4100U-S1 Programming Guide
Document: LT0400
Adding Zone Displays
Page 7-2
15 December 2010
Issue 1.4
7.1 General
This chapter describes how to add more zones to the configuration. It applies when an
existing 4100U-S1 panel is being upgraded to have more zones and the existing
configuration needs to be expanded to control them. Configuring zones for new sites where
the configuration is built for the 1
st
time is described in Chapter 4.
7.2 Zone Control and LED Modules
The basic hardware modules to provide zone LEDs and controls in a 4100U-S1 are:
4100-1282
– 8 Pushbuttons/16 Red-Yellow LEDs – provides 8 pushbuttons and 16
LEDs.
4100-1288/1289
– 64 LED / 64 SW Controller – slave module - controls 64 LEDs
and 64 switches i.e. 4 X 4100-1282 modules.
Other LED and switch modules are available for different applications (e.g. 4100-ME0456 4-
way AS1668 Control Module).
The standard configuration of a 4100U-S1 as it leaves the factory is to have 16 zones, which
means 1 X LED/switch controller (4100-1288) and 2 X LED/switch modules (4100-1282) are
fitted.
For every additional 8 zones an additional LED/switch module (4100-1282) needs to be
fitted and configured, and if the number of zones goes above 32 then an additional
LED/switch controller (4100-1288) needs to be configured.
For mounting and wiring instructions for these modules refer to the 4100U-S1 Installation
Manual (LT0394).
Note that when the 2
nd
LED/switch controller (4100-1289) is to be configured
– its
address must be set to 4 to match the template configuration.
7.3 Hardware Configuration Modification
To add new Zone Switch/LED and Controller modules to the configuration do the following:
Select the
HARDWARE
Tab
Click on the “
+
” sign beside
Unit 0
Click on the “
+
” sign beside
Box 1
Click on the “
+
” sign beside
Bay 2
This will show the currently configured display cards in
Bay 2
.