4100U-S1 Programming Guide
Document: LT0400
Addressable Device Settings
Page 6-8
15 December 2010
Issue 1.4
TRACK
ON
PRI
=
9
,
9
M1
-
7
-
1
| MRELAY | RELAY | TEST SOLENOID
[END OUTPUTS]
9)
Create another Custom Control equation, this time for the Print statement on the panel
display as follows:
[INPUTS]
STATUS
ON
M1
-
7
-
1
| MRELAY | RELAY | TEST SOLENOID
[END INPUTS]
[OUTPUTS]
ALL
"RELEASE BUTTON TO STOP SOLENOID TEST"
[END OUTPUTS]
10)
Alter CC equation 6-32 by changing the output statement from Hold to Track. This will allow
the Solenoid to turn off when the button is released.
[INPUTS]
STATUS
ON
P514
| DIGITAL | UTILITY | ALARM TEST
AND
STATUS
ON
P916
| DIGITAL | UTILITY | MULTIFUNCTION SWITCH - ZONE 16
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
9
,
9
P1016
| DIGITAL | FIRE | ALARM TEST ZONE 16
[END OUTPUTS]
TRIAM
– Flow Switch / Test Solenoid/ Valve Monitor
Repeat above but use WSO in place of WATER and wire a 1K8 Ohm resistor in series with
the normally open contacts of the monitor valve. The flow switch will give a S/C. Valve
Monitor will be a current limited S/C and be shown as an Isolate for AZF 16.
1)
Program a TRIAM – Utility (M1-7-0 in our example).
2)
M1-7-1 – MRELAY – Point Type RELAY – Test Solenoid.
3)
M1-7-2 – MTSENSE – Point Type
WSO – Flow Switch/ Monitor AZF 16.