4100U-S1 Programming Guide
Document: LT0400
Appendices
Page 12-10
15 December 2010
Issue 1.4
12.3.2
Alarm / Fault / Normal Test Button and LEDs
This button is used to select between Alarm Test, Fault Test and Normal operation for the
Multifunction buttons. The Alarm Test and Fault Test LEDs indicate what operation the
Multifunction buttons will initiate if pressed.
The Alarm and Fault Test code is stored in a separate Program to all other code. This
Program is enabled only if the panel is in Alarm or Fault Test mode.
References:
Push Button Mode
set to “PBH” Mode
Point Address:
0-5-1
Alarm Fault Test Normal (AFN) Button
P513
Status of AFN button
0-5-6
Alarm Test LED
P514
Active if panel is in Alarm Test Mode
0-5-13 Fault Test LED
P515
Active if panel is in Fault Test Mode
Equations:
3-12 Alarm Test Mode
[INPUTS]
STATUS
ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND
NOT
STATUS
ON
P514 | DIGITAL | UTILITY | ALARM TEST
AND
NOT
STATUS
ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD
ON
PRI
=
9
,
9
P514 | DIGITAL | UTILITY | ALARM TEST
HOLD
ON
PRI
=
9
,
9
P516 | DIGITAL | UTILITY | ALARM OR FAULT TEST ACTIVE
HOLD
OFF
PRI
=
9
,
9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
PANEL
"ALARM TEST READY-PRESS FOR FAULT TEST"
HOLD
ON
PRI
=
7
,
7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
[END OUTPUTS]
3-13 Fault Test Mode
[INPUTS]
STATUS
ON
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
AND
STATUS
ON
P514 | DIGITAL | UTILITY | ALARM TEST
AND
NOT
STATUS
ON
P515 | DIGITAL | UTILITY | FAULT TEST
[END INPUTS]
[OUTPUTS]
HOLD
ON
PRI
=
9
,
9
P515 | DIGITAL | UTILITY | FAULT TEST
HOLD
OFF
PRI
=
9
,
9
P513 | DIGITAL | UTILITY | ALARM TEST/FAULT TEST/NORMAL BUTTON
HOLD
OFF
PRI
=
9
,
9
P514 | DIGITAL | UTILITY | ALARM TEST
PANEL
"FAULT TEST READY-PRESS AGAIN FOR NORMAL"
[END OUTPUTS]