4100U-S1 Programming Guide
Document: LT0400
Appendices
Page 12-4
15 December 2010
Issue 1.4
12.2.2
Analog Points
Analog Points can have a value 0-65535 and can be used for Timers, Counters or store a
numerical value.
A0
– Number of Devices in Alarm
A1
– Number of Isolates
A2
– Number of Faults
A34
– System Startup pulse
A257
– Alarm and Fault Test Timeout
12.2.3
Lists
Lists are container objects used to group several points. A list inherits the states and status
of the points within the list and the list is used the same as a point.
L256
– Brigade call Alarm List
L257
– General Fire Trip List (ACF Isolatable)
L258
– Zone Alarm Test List
L259
– Zone Fault Test List
L260
– Zone Isolate Toggles
12.2.4
Physical Hardware Points (LEDs Relays etc)
Alarm Test Active LED or keyboard panel
(P514)
A/C Trip LED
(P521)
ACF Isolated LED
(P517)
Bells Isolated LED
(P518)
0-5-10
Warning System Isolated LED
(P519)
0-5-11
Common Alarm LED
0-5-13
Fault Test Active LED
(P515)
0-5-1
Alarm Fault Normal Button
(P513)
0-5-2
A/C Reset Button
(P522)
0-5-3
ACF Isolate Button
(P517)
0-5-4
Bell Isolate Button
(P518)
0-5-5
Warning System Isolate Button
(P519)
0-7-3
City Alarm Relay
0-7-4
City Alarm Trouble Relay
(FAULTS)
1-9
City Fire Relay 1
(ALARMS)
1-11
City Supervisory Relay 2
(ISOLATES)
1-12
City Trouble Relay 3
(FAULTS)
SIG3
ACF General Fire Trip
(SPS NAC 1)
SIG4
Fire Alarm Bell
(SPS NAC 2)
SIG5
Warning System
(SPS NAC 3)