4100U-S1 Programming Guide
Document: LT0400
Adding Zone Displays
Page 7-6
15 December 2010
Issue 1.4
7.4 Modify the Custom Control Equations for the Zones
The simplest method to add more custom control equations for the new displays is to open a
32 or 64 zones template and export the custom control equations for the zones, then from
within the original site configuration import these equations. The detailed steps are as follow:
1.
Click on the „
File
‟ menu and select „
Open
‟.
Browse
to the location containing the 3 default configuration templates supplied with
SF0369 and select the S1_64ZN.SDB4100U configuration if more than 32 zones (up to 64)
are needed, or select S1_32ZN.SDB4100U if the configuration should include up to only 32
zones. Click
OK
.
2. Click on the
„
Custom
Control
‟ tab. Right Click on
Program 4
and select „
Export
Program…
‟.
Save
the exported .CC4100U
file in an accessible location. .
At the end of the export process a message with the
process status will appear with the export result.
Click the OK button.
3.
Close the template and re-open the site configuration database.
4.
Click on the „
Custom Control
‟ tab.
Right Click on
Program 4
and select „
Import, Append Program…
‟ .
Browse
to the location where you saved the exported .CC4100U file, select it and click
„
Open’
.
The import process will start.
At the end of the import process, a message with the process status will appear with the
import result.
Click the OK button.