4100U-S1 Programming Guide
Document: LT0400
Appendices
Page 12-6
15 December 2010
Issue 1.4
3-7 Alarm Verification Timing / Start up
[INPUTS]
STATUS
ON
A34 | ANALOG | TIMER | SYSTEM STARTUP PULSE TIMER
[END INPUTS]
[OUTPUTS]
SET
CONSTANT
5
CNTS
A37 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - RETARD TIME
SET
CONSTANT
10
CNTS
A38 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - RESET TIME
SET
CONSTANT
180
CNTS
A39 | Set-Analog (Destination) | ANALOG | ANALOG | ALARM VERIFICATION - CONFIRMATION TIME
HOLD
OFF
PRI
=
7
,
7
P21 | DIGITAL | UTILITY | SMPL PROGRAM 5 - USER CUSTOM CONTROL
HOLD
ON
PRI
=
7
,
7
P478 | DIGITAL | UTILITY | INHIBIT DEVICE TROUBLES WHILE DISABLED
[END OUTPUTS
12.2.7
Brigade Relay Equations
The following are the equations used to drive the Alarm, Isolate and Fault Brigade Relays.
These
equations should not be modified without consulting a Simplex Technician.
References:
Point Address:
0-7-3
City Alarm Relay (relay on 4100+ type CPU motherboard)
0-7-4
City Trouble Relay (relay on 4100+ type CPU motherboard)
1-9
City Fire/Opt Relay 1 (Alarm relay on SPS piggyback board)
1-11
City SUPV/Opt Relay 2 ( Supervisory / Isolate relay on SPS piggyback board
1-12
City Fire/Opt Relay 3 (Trouble relay on SPS piggyback board)
A1
Number of Isolates on Panel
A2
Number of Faults on Panel
L256
Brigade Call Alarm List
3-1 ASE Alarm Relay
[INPUTS]
STATUS
ON
L256 | LIST | DPSEUDO | BRIGADE CALL ALARM LIST
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
7
,
7
0
-
7
-
3
| MCODE7 | RELAY | Master Output - City Alarm Relay
TRACK
ON
PRI
=
7
,
7
1
-
9
| SPECOUT | SPECOUT | CITY FIRE/OPT RELAY 1
[END OUTPUTS]
3-2 ASE Isolate Relay
[INPUTS]
STATUS
ON
A1 | ANALOG | ANALOG | NUMBER OF SYSTEM SUPERVISORIES
[END INPUTS]
[OUTPUTS]
TRACK
ON
PRI
=
7
,
7
1
-
11
| SPECOUT | SPECOUT | CITY SUPV/OPT RELAY 2
[END OUTPUTS]