97/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
23.04.2009
Operating line
Range
Fault text
Fault text for fault input 3
Fault input 3
0 / 1 (1 = fault)
[Main pump] overload
0 / 1 (1 = overload)
[Main pump B] overload
0 / 1 (1 = overload)
Flow signal pump
0 / 1 (0 = no flow)
Optg hours pump
0…99999 h
Optg hours pump B
0…99999 h
When making diagnostics or the wiring test, logic states are displayed. The input is
active when 1 appears on the display. If “Normal position open“ is selected, this is the
case when the contact is closed; if “Normal position closed“ is selected, this is the case
when the contact is open.
Main menu > Boiler sequence manager > Outputs
Operating line
Range
Mixing valve position
0…100%
Main pump
Off / On
Main pump B
Off / On
Main menu > Boiler sequence manager > Limitations
Operating line
Range
MBRT return min
Inactive / Active
Setpoint maximum limitation
Inactive / Active
6.8 Fault
handling
Number Text
Effect
330
Main flow sensor error
Urgent message; must be acknowledged
and reset, plant stop
331
Main return sensor error
Nonurgent message; must be acknowl-
edged, no plant stop
Number Text
Effect
2491
[Main pump] overload
Nonurgent message; acknowledgement
can be parameterized; factory setting:
”Acknowledge“
2492
[Main pump B] overload
Nonurgent message; acknowledgement
can be parameterized; factory setting:
”Acknowledge“
2493
[Main pump] no flow
Nonurgent message; must be acknowl-
edged and reset
2494
[Main pump B] no flow
Nonurgent message; must be acknowl-
edged and reset
2495
[Main pump] fault
Urgent message; must not be acknowl-
edged, plant stop
Number Text
Effect
2391
[Boiler seq] water shortage
Can be parameterized
2392
[Boiler sequence] over-
pressure
Can be parameterized
2393
[Boiler sequence] under-
pressure
Can be parameterized
Fault of main flow and
main return sensor
Fault of main pump
Fault supervision
boiler sequence