55/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
4 General settings
23.04.2009
4.5.2 Aggregate
names
Aggregates boiler 1…6, primary controller, heating circuit and time switch can be given
dedicated names. The setting is made on the relevant aggregate.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler 1
Operating line
Range
Factory setting
Boiler 1
Max. 20 characters
Here, text with a maximum of 20 characters can be entered. This designation is then
used on the info pages and by the menus. Only in the extra configuration and in the
wiring test will the original designation boiler 1 continue to be used.
4.5.3
Text of fault inputs
The texts for the fault inputs are locally displayed as fault texts and are also transmitted
via bus.
In addition to the predefined fault inputs, there are 4 universal fault inputs and 3 digital
aggregate-related fault inputs available. The text for the universal fault inputs can be
edited on
Main menu > Settings > Faults
, the text for the aggregate-related faults at the
relevant aggregate, e.g.
Settings > Boiler 1 > Fault settings
.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Faults > Fault input 1
(or
2
,
3
or
4
)
Operating line
Range
Factory setting
Fault text
Max. 20 characters
[Fault input 1]Fault
Fault text
Max. 20 characters
[Fault input 2] Fault
Fault text
Max. 20 characters
[Fault input 3] Fault
Fault text
Max. 20 characters
[Fault input 4] Fault
4.5.4
Electronic business card
The text of the electronic business card is displayed as an Info picture. The electronic
business card must be activated in the extra configuration.
Main menu > Commissioning > Extra configuration > Miscellaneous
Operating line
Range
Factory setting
Business card
Yes / No
Yes
Main menu > Commissioning > Settings
… or
Main menu > Settings > Texts
Operating line
Range
Factory setting
Business card line 1
Max. 20 characters
Business card line 2
Max. 20 characters
Business card line 3
Max. 20 characters
Business card line 4
Max. 20 characters
Setting (example
for boiler 1)
Setting (example for
fault input 1)
Settings