178/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
23.04.2009
The type of room temperature sensor can be selected (example with input terminal
RMK770.X4):
Main menu > Commissioning > Settings >
… or
Main menu > Settings > Inputs > RMK770.X4 > Type
The following choices are available:
•
LG-Ni1000
•
2 × LG-Ni1000
•
T1
•
Pt1000
•
DC 0…10 V
A maximum of 2 LG-Ni1000 sensors can be connected to the same terminal. The
controller does not automatically identify that. For this reason, in that case, 2 × LG-
Ni1000 must be selected when parameterizing the terminal inputs..
If the controller is connected to the bus, the room temperature signal can be sent or
received via bus. In addition to the room zone, a valid device address must be set on
the controller.
With default address 255, there is no communication via the bus.
If the room temperature is acquired by the unit, it is delivered via bus in the heating
circuit’s room zone (geographical zone apartment) so that it is made available to all
devices on the bus.
The room temperature can also be acquired by bus-compatible room sensors or room
units (e.g. QAW740) and sent directly via bus. The associated room zone (geographical
zone apartment) is to be set on the sensor or the room unit.
The room temperature signal sent via bus is received by the heating circuit, provided
the room zones (geographical zone apartment) of the transmitter and the recipient
agree.
The following variants are available:
Variant Effect
Diagram
1 room sensor directly
connected
The heating circuit operates
with its own room temperature.
When communication is
activated, the room tempera-
ture is sent across the geo-
graphical zone of the heating
circuit.
T
Synco
2 room sensors directly
connected
The heating circuit operates
with the average of the 2
sensors. When communication
is activated, the average value
is delivered as the room
temperature across the heat-
ing circuit’s geographical zone.
Synco
T
T
1 room sensor (or 1
room unit QAW740)
When communication is
activated, the heating circuit
receives the room temperature
of the same geographical
zone.
The heating circuit operates
with the average of the 2
temperature signals received.
T
Synco
Type of sensor
Room temperature
via bus
Sending
Receiving