Boiler sequence controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
23.04.2009
31
31
D
3
8
off
on
Pump
TR
TRx
TRw
TRw + TR - TRSD
TRw + TR
TR
on
off
TRSD
TRw
TR
t
t
Temperature differential for switching the heating circuit off
Δ
TR Time
TR
Room temperature
TRSD Temperature differential for switching the heating circuit on
TRw
Room temperature setpoint
TRx
Actual room temperature
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Limitations
Operating line
Range
Factory setting
Room limitation increase
---- (none) / 0.5…5.0 K
----
Room lim switching differential
0.2…5.0 K
0.5 K
The room limitation increase is used to set the temperature differential for switching the
heating circuit off.
The room switching differential is used to set the temperature differential for switching
on the heating circuit.
10.8.2 Return temperature limitation
The heating circuit’s mixing valve can be used to ensure maximum limitation of the
return temperature. Minimum limitation is not supported.
Y1
B1
M1
B7
31
3
3S79
B1
Flow sensor
B7
Return sensor
M1
Heating circuit pump
Y1
Heating circuit mixing valve
The function is activated via the extra configuration:
… > Heating circuit > Inputs > Return sensor
Assign terminal
Settings
Room limitation increase
Room lim switching
differential
Extra configuration