122/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler control
23.04.2009
The terminals still available for selection are the free terminal pairs (Q1/Q2, Q3/Q4,
Q5/Q6) for the open and the close signal. Normally, special terminal pairs are required
for that purpose (RC units for radio interference suppression; for more detailed informa-
tion, refer to subsection 3.3.2 “Terminal assignment and properties of outputs”).
By selecting “Maint boiler return temp mod“, a mixing valve with DC 0…10 V output is
assigned. If required, this output can be matched to the type of mixing valve used.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Limitations
Operating line
Range
Factory setting
Boiler return temperature min
---- / 8…140 °C
---- °C
To adapt the control parameters to the type of plant (actuator and controlled system),
the same setting parameters as those used with the mixing heating circuit are available.
For more detailed information, refer to section 5.7 “Mixing valve control”.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler … > Return control
Operating line
Range
Factory setting
Actuator running time
1…600 s
150 s
P-band Xp
1…100 K
50 K
Integral action time Tn
0…600 s
60 K
If a minimum return temperature shall be ensured, it is necessary to select the minimum
boiler temperature accordingly. The minimum boiler temperature must be at least a few
K higher than the minimum return temperature.
In the case of plant with a mixing valve for the maintained boiler return temperature, the
mixing valve is driven to the fully closed position if the return temperature sensor is
faulty and then deenergized to make possible manual adjustment.
If no return temperature sensor is configured, a fault status message appears.
If only a return temperature sensor is configured with no mixing valve present, the
sensor is used for display purposes.
7.11 Flue gas temperature supervision
If the flue gas temperature shall be monitored, a sensor must be configured in the extra
configuration.
Main menu > Commissioning > Extra configuration > Boiler … > Inputs
Operating line
Adjustable values / remarks
Flue gas temperature sensor
Assign input
It is to be noted here that for the temperature inputs, a Ni1000 sensor is configured as
standard. However, for flue gas temperature measurements, Pt1000 sensors are often
used; for this reason, Pt1000 is set here as a default value. The type of sensor can be
adapted under
Settings > Inputs
at the configured terminal.
As a result of the sensor’s configuration, the following functions are made available:
This function is active whenever a flue gas temperature sensor is selected.
Main menu > Boiler … > Inputs/setpoints
Operating line
Range
Flue gas temperature maximum
---- / 8…400 °C
It is always the maximum flue gas temperature that is saved and displayed. On the
menu line that shows the value, the value can be reset to “----“ (representing 8 °C) so
that the current value is adopted again.
Configuration of a pair of
terminals for a 3-position
mixing valve
Return temperature
setpoint
Fault of return tempera-
ture sensor
Slave pointer function