CE1P3132en
HVAC Products
8 Heat demand and heat requests
23.04.2009
31
31
D
2
0
1
2
Outside
temperature
Flow temperature
(Curve point 1):
Outside temp.
Max. flow temp.
readjustment
(Curve point 1):
Flow temp.
(Curve point 2):
Flow temp.
(Curve point 2):
Outside temp.
The adaptation of the flow temperature can be set as follows:
•
The speed of flow temperature readjustment can be set under
> Demand control >
Control action
•
The kind of evaluation of the consumers’ valve positions can be selected under
>
Demand control > Request evaluation
−
When using the “Maximum” setting, the flow temperature is readjusted such that
the valve position of the consumer with the greatest heat demand is 90%.
−
When using the “Average” setting, the flow temperature is readjusted such that
the valve positions of the 4 largest consumers will be 90% on average.
This setting does not ensure that the heat demand from all consumers can be sat-
isfied. But it prevents an individual consumer from forcing the flow temperature to
a high level (e.g. because a window was left open).
The heating curve settings of the heat demand transformers also apply to the heat
request contact of the heating curve (operating line
Heating curve request 2-pos
).
Both “On range“ and “Off range“ depend on the settings:
Limit value request on
Limit value request off
OFF…100 Setting
range for limit value request On (e.g. OFF = 30%)
0…ON
Setting range for limit value request Off (e.g. ON = 45%)
Adaptation of flow
temperature
Note
Setting the limit value
request