44/232
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
23.04.2009
The digital inputs can accept signals from potential-free contacts for control functions.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Setting
N.X5 Digital
The normal position can be predefined for each digital input.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > …X…
Operating line
Range
Factory setting
Normal position
Open / Closed
Open
G
G
G0
X...
G0
N
31
4
0A
0
5
AC
24
V
M
F...
Δ
p
X...
M
F...
Digital signals cannot be monitored.
3.5
Several boiler sequence controllers RMK770
If the number of outputs do not suffice although all extension modules are fully used, or
if the number of available function blocks do not suffice, the multiboiler plant must be
assigned to several RMK770 controllers. But there may also be other reasons to have
the plant controlled by several RMK770.
In that case, one of the RMK770 controllers provides the boiler master function. And
function block “Boiler sequence manager” is activated only in that RMK770. This func-
tion block controls the boilers of the other RMK770 via bus.
The boiler master is defined by configuring the main flow temperature sensor.
With the other RMK770 controllers, that sensor must not be configured.
Configuration with the second RMK770 is made with setting “Basic type K“. In the extra
configuration, the sensors and aggregates must be assigned to the relevant boiler. In
the illustration below, this is boiler no. 3.
T
T
T
T
31
32
S
4
3
CE-
Q11
D1
X8
Q24
Q23
G0
M
M
Y1
G1
G
G1
X6
M
X5
M
M
M
X3
X2
M
X4
M
Q33
Q34
Q41
Q44
Q53
Q54
Q63
Q64
Q14
CE+
X1
G1
Q12
Q42
Q73
Q74
Y2
G0
X7
D2
M
M
G1
G0
G1
RMK770
T
RMZ78…
1
2
3
Digital inputs
Configuration of input
Normal position
Setting
Fault handling