Boiler sequence controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
23.04.2009
The temperature request for the current heat demand is calculated based on the flow
temperature setpoint of the heating circuit (refer to subsections 10.5.2 “Heating curve”
and 10.5.3 “Influence on the flow temperature setpoint”) plus an adjustable setpoint
increase for the mixing valve.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Mixing circuit controller
Operating line
Range
Factory setting
Setp increase mixing valve
0…50 K
10 K
Setpoint increase mixing valve is used to define by what amount the temperature
request (to the boiler or the primary controller) shall be raised against the flow tempera-
ture setpoint.
10.10 Extra functions
10.10.1 Text designations
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit
Operating line
Range
Factory setting
Heating circuit
Max. 20 characters
Heating circuit
Time switch
Max. 20 characters
Time switch
The texts entered here appear on the menu and on the info display in place of the initial
texts.
10.10.2 Acquisition of the room temperature
For the optimization functions and/or the influence on the flow temperature setpoint, the
room temperature is required.
The input is configured via the extra configuration:
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs > Room sensor
Assign terminal
A heating circuit can handle a maximum of 2 room temperatures. It is of no importance
whether the room temperature is acquired locally or via KNX bus.
The average is generated from the 2 actual values.
Setpoint increase
mixing valve
Extra configuration
Averaging