153/232
Building Technologies
Boiler sequence controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
23.04.2009
Preselection Use
Economy
This operating mode is suited when the room is not occupied for
a few hours or when a reduced room temperature is desired.
Economy mode is usually selected for the night
Protection
With this operating mode, the room is heated only when there is
risk of frost, which could lead to frozen pipes, etc. The room
temperature is maintained at a level above 0 °C.
The room temperature setpoint depends on the room operating mode. The flow tem-
perature setpoint, the heating limit and the optimization functions are influenced by the
current room temperature setpoint.
Main menu > Heating circuit > Room operating mode
Operating line
Range
Factory setting
Preselection
Comfort
Precomfort
Economy
Protection
State
Comfort… Protection
Cause Time
switch
Holidays
l
or
Special day
k
or
Timer function
i
or
j
Room unit presence
button
h
Room operating mode
selector
g
Room operating mode
contact
f
External master
e
The control priorities
e
… are explained in subsection 10.3.7 “Control priorities in the
heating circuit”.
Here, the plant operator can select the required operating mode. In operating mode
, the setpoint is determined by the time switch or the plant operator. If required,
it can be switched to continuous operation with a fixed setpoint.
In Protection mode, safety-related functions, such as frost protection, remain active.
The display shows the heating circuit’s setpoint that is currently maintained.
There may be various reasons for the current state. Decisive is the control priority (refer
to subsection 10.3.7 “Control priorities in the heating circuit”).
In
mode, the time switch switches the room operating mode or the setpoint
according to the program entered. During the holiday period, the setpoint is predefined.
Main menu > Heating circuit > Room operating mode
Operating line
Range
Factory setting
Room operating mode holidays
Economy / Protection
Economy
The holiday function is only active in
mode.
Room operating mode
Preselection
Room operating
mode selector
⇒
State
Cause
Time switch
Holiday operating
mode
Note