2. Set P001: Operation (measurement mode)
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
Value
1 *
Level returns distance to material level referenced from Empty (process empty level). The
reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
2
Space returns distance to material level referenced from Span (process full level).
3
Distance returns distance to material level from reference point.
Level
(P001 = 1)
Space
(P001 = 2)
Distance
(P001 = 3)
Distance
Space
Level
P007
P006
100%
(20 mA)
(20 mA)
100%
0%
(4 mA)
(4 mA)
0%
100%
(20 mA)
(4 mA)
0%
Empty
Span
Span
Empty
Span
Empty
mA Output with Level, Space, and Distance operation
reference
point
3. Set P003: Measurement Response
Set P003 to a measurement response speed
just faster than the maximum filling or
emptying rate (whichever is greater).
(P004 - view only)
4. Select measurement units (P005)
Value
1
*
slow
0.1m/minute
2
medium
1m/minute
3
fast
10m/minute
Value 240 *
rod antenna
Value
1 *
meters
2
centimeters
3
millimeters
4
feet
5
inches
Summary of Contents for SITRANS LR
Page 1: ...Quick Start Manual 12 2012 SITRANS Radar Transmitters SITRANS Probe LR ...
Page 2: ......
Page 18: ...Page EN 16 SITRANS Probe LR QUICK START MANUAL A5E32106153 mmmmm English Notes ...
Page 34: ...Side DA 16 SITRANS Probe LR KVIKSTART MANUAL A5E32106153 mmmmm Dansk Bemærkninger ...
Page 50: ...Seite DE 16 SITRANS Probe LR KURZANLEITUNG A5E32106153 new mmmmm Deutsch Notizen ...
Page 82: ...Página ES 16 SITRANS Probe LR PUESTA EN MARCHA RÁPIDA A5E32106153 mmmmm Español Notas ...
Page 98: ...Page FR 16 SITRANS Probe LR MISE EN SERVICE SIMPLIFIEE A5E32106153 mmmmm Français Notes ...
Page 114: ...Pagina IT 16 SITRANS Probe LR AVVIO RAPIDO A5E32106153 mmmmm Italiano Annotazioni ...
Page 146: ...Página PT 16 SITRANS Probe LR MANUAL DE PARTIDA RÁPIDA A5E32106153 mmmmm Português Notas ...
Page 162: ...Sivu SU 16 SITRANS Probe LR PIKAKÄYTTÖOPAS A5E32106153 mmmmm Suomi Huomautukset ...
Page 178: ...Sida SV 16 SITRANS Probe LR MANUAL FÖR SNABBSTART A5E32106153 mmmmm Svenska Anmärkningar ...