Note
HMI timeout
If no key is pressed for 10 minutes, the display switches to show operation view. If Backlight is
set to Automatic, display backlight goes off automatically 30 seconds after the last keypress.
Note
Operation does not require opening of the device. This means that the high degree of protection
of IP67 and safety in hazardous areas are guaranteed at all times.
6.3.2
Wizard introduction
In this chapter it is described how to commission the device via the local display (HMI) using the
Quick Commissioning wizard.
For further information on how to navigate the wizards, refer to Wizards (Page 88).
In the wizard graphics below, the HMI view numbers are stated to the left.
The first view in each wizard (About - view 1) is a description of what settings/actions can be
performed using the specific wizard.
The last view in each wizard (Finished) shows that the last step of the wizard was completed.
Any parameter changes confirmed with are saved immediately.
At any time in any wizard selecting Exit will bring you back to the main wizard menu without
discarding changes.
6.3.3
Initial startup
The first time the device is powered up, you will be prompted to set the language. The device
always starts up showing language in English. When the language has been set, you will be
prompted to set the date and time.
After confirming/changing the date and time you will be asked if you want to start the Quick
commissioning wizard. If you choose Yes (recommended), the Quick commissioning wizard
will start. If you choose No, you accept the default values of the device, and the next HMI view
will be the operation view 1.
Commissioning
6.3 Local commissioning via HMI
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB