Bidirectional flow with symmetrical scaling
)&
v
v
mA
Kg/h
v
v
v
v
v
P$
P$
P$
P$
P$
NJK
NJK
NJK
NJK
①
Upper scaling
②
Lower scaling
③
Low flow cut-off
④
Upper alarm value
⑤
Maximum measurement value
⑥
Upper range
⑦
Lower range
⑧
Minimum measurement value
⑨
Measurement range
Current output setting
● Process value = Mass flow
● Direction = Bidirectional (Symmetric)
● Current Mode = 4-20 mA NAMUR
● Upper Scaling = 400 kg/h
● Lower Scaling = 100 kg/h
● Fail Safe Mode = Maximum current
● Low Flow Cut-Off = 25 kg/h
8.2.6.2
Pulse output
The pulse output function supplies pulses equivalent to a configured amount of accumulated
volume or mass. The pulse width is configured and the pulse repetition is proportional to the
selected flow rate.