Mounting on pipe
1. Mount mounting bracket with cushion pad on pipe using fastening brackets/U-bolts and
supplied pipe adaptor. Note: U-bolts and other miscellaneous hardware are not supplied
with the flowmeter.
2. Tighten nuts (torque: 10 Nm).
Mounting the transmitter
1. Remove locking cap from mounting bracket.
2. Mount transmitter on mounting bracket taking care that the flutes on the mating faces are
correctly engaged.
3. Firmly tighten locking cap on mounting bracket (torque: 25 Nm).
4.2.1.2
Wall mount housing
Mounting on wall
Note
Mounting screws are not included
You will need four screws, able to support at least 55 lbs (25 kg). Siemens recommends
M6x100 screws with appropriate anchors for the wall material.
Installing/mounting
4.2 Installation instructions
SITRANS FC330
42
Operating Instructions, 01/2019, A5E44030648-AB