
1. Check with table in Product compatibility (Page 10) if you have the most recent version of
the EDD. If necessary, update the EDD as described in SIMATIC PDM (Page 123).
2. Set "Address" via handheld programmer (default for PROFIBUS PA is 126).
– In "PROGRAM mode", navigate to your field device, for example to: "Product name" >
Communication > Device Address.
– Press RIGHT arrow twice, to open parameter view and enable "Edit mode".
– If required, key in a new value and press RIGHT arrow to accept it.
The display shows the new value.
– Press "Mode" to return to "Measurement mode".
3. Launch SIMATIC Manager and create a new project.
4. Go to the menu "Device > Master Reset".
5. Click on "Factory Defaults".
6. After the reset is complete click on "Close".
7. Upload parameters to the PC/PG.
8. Configure the device via the Quick Start wizard.
Open in SIMATIC PDM the menu Device – Set Address, enter a value for New Address, and
click on Assign Address.
Operating
7.2 Remote operation
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB
125