ID
Icons
Message
Cause/Action
179 Icons
de‐
pend‐
ing on
simula‐
tion
Alarm class simulated
Disable the simulation to return to normal operation.
180
Internal error in transmitter Restart the device. If the problem persists, replace the
component.
181
SensorFlash error
Replace the SensorFlash.
182
Transmitter firmware in‐
compatible
The component does not have the expected firmware ver‐
sion. Update the product firmware or replace the compo‐
nent.
192
Dosing monitoring time
exceeded
Check the dosing system. If it is ok, increase the parameter
value 'Duration time'.
193
Dosing overrun limit ex‐
ceeded
Check the dosing system. If it is ok, increase the parameter
value 'Overrun value'.
194
Dosing possibly inaccu‐
rate
Invalid process value during dosing. For further informa‐
tion, check the diagnostic log.
195
CH2 loop current in lower
saturation
The process value is so low that the loop current reaches
the lower saturation limit and cannot decrease any further.
Check process conditions. Adjust parameter value 'Lower
range value'.
196
CH2 loop current in upper
saturation
The process value is so high that the loop current reaches
the upper saturation limit and cannot increase any further.
Check process conditions. Adjust parameter value 'Upper
range value'.
Diagnostics and troubleshooting
10.2 Fault codes and corrective actions
SITRANS FC330
Operating Instructions, 01/2019, A5E44030648-AB